Transformer Oil Testing: DGA, Moisture and Dielectric Strength is the practice of sampling and analysing the mineral insulating oil inside an oil-immersed transformer to judge the condition of the oil, the paper insulation and the active part without opening the tank. Because the oil both insulates and cools, and because it circulates past every winding and connection, it carries a chemical record of thermal, electrical and moisture problems. A structured test programme turns that record into early warning, letting you plan intervention before a fault becomes a failure.
Insulating oil ages and reacts to stress. Heat, electrical discharge and contact with cellulose paper break molecular bonds, releasing dissolved gases and by-products. Moisture ingress lowers breakdown strength and accelerates paper degradation. Oxidation raises acidity and forms sludge. Each mechanism leaves a measurable signature, so a small oil sample gives a wide view of internal health. This is why oil analysis sits alongside electrical diagnostics such as partial discharge testing in any serious transformer condition programme.
Screening tests characterise the oil itself. They are cheaper and faster than full gas analysis and are usually run at every routine visit.
Exact limits depend on voltage class and standard. IEC 60422 gives category tables; the values below are indicative for a general power transformer.
| Property | Method | New oil | Investigate |
|---|---|---|---|
| Breakdown voltage | IEC 60156 (2.5 mm gap) | > 60 kV | < 40 kV |
| Water content | IEC 60814 (Karl Fischer) | < 10 ppm | > 20 to 30 ppm |
| Acidity | IEC 62021 | < 0.03 mg KOH/g | > 0.15 mg KOH/g |
| Interfacial tension | ASTM D971 | > 40 mN/m | < 25 mN/m |
DGA is the diagnostic core. A degassed oil sample is analysed by gas chromatography (ASTM D3612) to measure fault gases dissolved in the oil. The pattern and ratios of gases identify the type of fault, while absolute concentrations and rate of change indicate severity. Interpretation frameworks include IEC 60599, the Duval Triangle (which uses methane, ethylene and acetylene), and IEEE C57.104, whose 2019 revision leans on statistical percentile limits and gassing rates rather than fixed thresholds alone.
Each fault temperature releases a characteristic gas mix. Low-energy events favour hydrogen and methane; hotter faults produce ethylene; only high-energy arcing produces significant acetylene. Carbon oxides point specifically at cellulose paper.
| Key gas | Formula | Indicated fault |
|---|---|---|
| Hydrogen | H2 | Partial discharge and corona |
| Methane | CH4 | Low-temperature overheating, PD |
| Ethane | C2H6 | Moderate thermal fault |
| Ethylene | C2H4 | High-temperature overheating (hot metal) |
| Acetylene | C2H2 | High-energy arcing |
| Carbon monoxide | CO | Cellulose (paper) degradation |
| Carbon dioxide | CO2 | Cellulose ageing and oxidation |
Any measurable acetylene deserves urgent attention because it implies arcing energy high enough to threaten the winding. Rising carbon oxides with a falling CO2 to CO ratio suggest active paper overheating. Faults located near a load tap changer need care in interpretation, since a diverter switch generates arcing gases by design; see tap changers and voltage regulation for context on why compartment separation matters.
Gases show what is happening now; furans show cumulative paper wear. As cellulose depolymerises it releases furanic compounds, chiefly 2-furaldehyde (2-FAL), measured by HPLC per IEC 61198. Furan concentration correlates with the degree of polymerisation of the paper, so it estimates remaining insulation life that DGA alone cannot. Furan testing complements electrical insulation diagnostics such as the polarization index when assessing end-of-life risk.
Results are only as good as the sample. Draw oil from the bottom sampling valve into a clean, oil-rinsed container, flush the valve first, and for DGA use a gas-tight glass syringe or metal cylinder that excludes air. Record oil and ambient temperature and load. Routine intervals are typically annual for screening and DGA on important units, tightened to quarterly or monthly when a gassing trend appears, and repeated within days if acetylene rises sharply.
Tracking these results manually across a fleet is where data gets lost. A maintenance platform such as Fabrico can schedule sampling, hold trend history per asset and trigger alerts on gassing rates. Book a Fabrico demo to see how oil-test history fits a wider reliability programme.
Important transformers are usually screened and DGA-tested annually. Increase frequency when a gas trend, low breakdown voltage or high moisture appears, and re-sample within days if acetylene or hydrogen rise steeply.
Acetylene forms only at very high temperatures, so its presence indicates high-energy arcing inside the tank. Even a few ppm warrants investigation because arcing can damage windings quickly.
IEC 60422 covers in-service mineral oil supervision, IEC 60599 and IEEE C57.104 cover DGA interpretation, and ASTM D3612 covers the gas extraction method. Individual properties have their own methods such as IEC 60156 for breakdown voltage.
Partly. Carbon oxide gases signal active paper stress, while furan analysis (2-FAL) correlates with the degree of polymerisation, giving an estimate of remaining cellulose life that gas analysis alone cannot provide.
Zakažite sastanak KSNUMKS-to-KSNUMKS sa našim stručnjacima ili se direktno upišite u naš besplatni plan.
Nije potrebna kreditna kartica!