Key takeaways
ATEX splits the work in two. Directive 2014/34/EU governs the equipment: the manufacturer certifies that the motor, junction box or luminaire meets its category when it leaves the factory. Directive 1999/92/EC (often called ATEX 137) governs the workplace: the employer must keep explosion protection effective in use, which means verified installation and ongoing inspection for the whole life of the installation. It is the same split the EU applies to machines generally under the EU Machinery Regulation 2023/1230: the manufacturer certifies at sale, the user carries the duties in service.
The certificate on the nameplate only describes the day the item was built. Gaskets harden, glands loosen, enclosures corrode, and somebody in year six fits a non-Ex replacement from the shelf. IEC 60079-17 is the standard that turns the employer's duty into a workable regime of grades, types and intervals. If zones and categories are still open questions on your site, start with our guide to hazardous area classification; everything below assumes the classification drawings already exist.
An inspection without tools or access equipment. It finds what a trained eye can see from the ground: obvious damage, corrosion, missing bolts, unauthorised modifications, dust accumulation, and obscured or missing certification labels. It cannot find a loose terminal, a hardened gland seal or a corroded flamepath: those live behind the lid.
Everything the visual grade covers, plus tools and access equipment where needed: steps to reach mounted items, spanners to confirm glands and covers are tight, a check of cable integrity and earth bonding. The enclosure stays shut and the circuit stays live, so no isolation is needed.
The enclosure is opened, which in practice means the circuit is isolated first. Only this grade can verify terminal tightness, internal moisture and corrosion, seal condition, correct lamp or element ratings, and the state of flamepath joints on Ex d equipment. It is the most expensive grade and the only one that proves internal condition.
The grades are cumulative: each includes everything below it. A regime built only on visual sweeps therefore misses the defect categories that matter most, glands and internals above all.
The selection logic is simple: harsher environments, more vibration, more corrosion and higher findings rates push toward higher grades and shorter intervals; benign indoor service with a clean history earns the longer end. Whatever comes out of the assessment, the schedule belongs in the same preventive maintenance plan as the rest of the asset base, not in a spreadsheet only the responsible person can find.
IEC 60079-17 requires inspectors to hold demonstrated, maintained competence: the protection concepts they inspect, the principles of area classification, and the practical skill to judge what they see. The concepts differ enough that competence in one does not transfer: the inspection points on an intrinsically safe loop (barrier parameters, cable segregation, earthing) have almost nothing in common with the flamepath and fastener checks on an Ex d enclosure. Ex personnel certification schemes are the common evidence, but the duty is competence itself, kept current through reassessment. Track who holds which Ex competence, and when it expires, in your maintenance skills matrix: an inspection signed by someone who cannot evidence competence is itself a finding.
The backbone of the regime is the equipment register: every Ex item on site, uniquely tagged. Per item, a defensible record holds:
This is exactly the shape of work a CMMS holds well. In Fabrico, each Ex item is an asset with its marking and certificate details on file, the visual, close and detailed inspections run as recurring PM tasks with grade-specific checklists, as-found and as-left values are stored per item, a failed checklist line can trigger a follow-up task, and the full history sits behind each asset when the auditor asks. To see the register and inspection cycle set up on your own asset list, book a short demo.
A food ingredients plant has 342 Ex items: 218 in zone 22 (organic dust in the milling and bagging halls) and 124 in zone 2 (a solvent handling area). The classification drawings were finished last year; nothing had ever been inspected per item.
Total steady-state effort: roughly 150 close- and detailed-grade inspections a year, plus the annual visual sweep, instead of a 342-item panic before every audit.
At the interval your own documented assessment sets, based on environment, manufacturer guidance and findings history. For periodic inspections the interval is commonly capped at 3 years, with the applicable edition of IEC 60079-17 and national rules deciding the exact ceiling. Continuous supervision by skilled personnel is the recognised alternative to a fixed cycle.
Visual (no tools, no access equipment: surface condition, labels, obvious damage), close (tools and access equipment, enclosure stays shut: glands, fasteners, bonding) and detailed (enclosure opened, normally with the circuit isolated: terminals, seals, internal condition, flamepaths). Each grade includes everything the lower grades cover.
Personnel with demonstrated, maintained competence in the protection concepts being inspected, plus a working knowledge of area classification. Recognised Ex personnel certification schemes are the usual evidence, but the requirement is competence itself, reassessed regularly and recorded per person.
Yes. Zone 22 carries the same inspection duty as any other zone, and dust service adds its own failure modes: layers that insulate enclosures and raise surface temperatures, and housekeeping that hides labels and damage. Dust zones are where visual sweeps earn their keep between deeper inspections.
An equipment register covering every Ex item, and per item: location and zone, protection type with full marking and EPL, certificate reference, the grade, type, date and inspector of each inspection, the result, and every defect with its close-out. The records must show both that inspections happened and that the chosen grades and intervals are justified.