Key Takeaways: An overload relay trips because the motor drew more current than its safe thermal limit for too long. That is a symptom with only a handful of real causes: a mechanical overload on the driven equipment, low or imbalanced supply voltage, single-phasing, a wrong relay setting or class, or excessive ambient heat. Diagnosis starts with a clamp meter on all three phases, compared against the motor's nameplate full-load amps, before anything gets replaced.
The overload relay models the motor's winding temperature from the current flowing through it. Sustained current above the dial setting means the windings are heating toward insulation damage, so the relay opens the contactor circuit. It is slow by design (thermal), unlike a breaker or fuse that reacts to short-circuit current instantly. A tripping overload relay is therefore telling you the motor has been working too hard for too long, not that a momentary spike occurred.
The lasting fix addresses the current draw, not the trip. Repair the mechanical cause, correct the supply problem, set the relay to nameplate values, and document each trip in your CMMS with the measured currents, so the third trip on the same conveyor becomes a work order for a bearing, not another reset. Trending motor current through condition monitoring catches the load creeping up weeks before the trip. And because operators often just reset and restart, these events vanish from manual logs: Fabrico's computer-vision-verified OEE records every one of these short stops with true duration, which is how repeated "small" trips finally show up as the capacity loss they are.
Can I just press reset and keep running?
Once, while you plan the measurement. Repeated resets without diagnosis cook motor insulation and convert a bearing-sized repair into a motor-sized one.
Is it ever correct to increase the relay setting?
Only up to the motor nameplate full-load current per the wiring scheme. Setting a relay above nameplate to stop nuisance trips removes the motor's protection.
The motor trips only on hot afternoons. Why?
Panel or ambient heat is shifting the thermal model, or the supply sags at peak load times. Check enclosure ventilation and afternoon voltage.
To see how automatic capture of every stop, even the two-minute resets nobody logs, changes your view of real capacity, book a demo.