Key takeaways
Windings die from heat. Sustained overcurrent, a jammed load, a lost phase or chronic undervoltage all push more current through the stator than its insulation can dissipate, and insulation life halves roughly every 10 °C of sustained overtemperature.
The thermal overload relay models that heating: bimetal elements (or an electronic model of them) integrate current over time and open the contactor's control circuit when the accumulated heat says the motor is in danger.
What it does not do: clear short circuits. Fault current protection comes from the upstream breaker or fuses; the overload relay and the short circuit device are a coordinated pair, not alternatives.
A 15 kW, 400 V conveyor motor, nameplate FLC 29 A, direct on line, measured start time 12 seconds at about 6 times FLC:
Rising running current at constant load means rising mechanical drag or electrical trouble: seized rollers, a dragging brake, a failing bearing, low voltage or phase imbalance. That is why trip events belong in the machine history with the measured currents attached, not in an operator's memory.
Trips correlated with current readings and recent work orders turn "the relay is oversensitive" into "current has crept 20 percent since March", which is a maintenance argument with a date on it, visible in the machine's MTBF trend months before failure.
Electrical checks travel together: when a trip brings you to the starter, the same visit is the moment for a quick insulation resistance test if the motor is suspect (lock out and tag out the starter, verify it dead with a meter, and disconnect the motor leads first), and a look at whether the duty has outgrown a direct start; our comparison of soft starters versus VFDs covers when a gentler start solves both the trips and the mechanical stress.
Recurring trips on one asset should open a work order every time, which is exactly the discipline a preventive maintenance plan in a CMMS helps enforce. To see how Fabrico ties trip events, readings and work orders to one asset, read how Fabrico tracks downtime.
Fabrico is software for OEE, downtime tracking and maintenance. We do not sell parts or repair services.
The setting is not a trip point. Under IEC 60947-4-1 a thermal overload relay must not trip at 1.05 times the set current and must trip at 1.2 times the set current within two hours.
A relay set to 29 A should therefore carry about 30.4 A without tripping and trip within two hours at about 34.8 A. Between those two figures it may or may not trip, which is why a slowly rising running current causes occasional trips long before it causes constant ones.
Pick a relay whose adjustment range contains the setting with some room on both sides. For a 29 A setting that means a range of roughly 23 to 32 A, not one where 29 A sits at the very end of the scale.
In a star delta starter, check where the relay is wired before you set it. Placed in the delta (phase) circuit, it is set to 0.58 times the motor rated current. Placed under the line contactor, as Schneider Electric shows for Type 2 coordination, it is set to the full motor rated current.
The nameplate current is always the first choice. When it is missing or unreadable, estimate the full load current from the motor power: I = P / (1.73 × U × cos φ × η). For the 15 kW, 400 V conveyor motor, assuming a power factor (cos φ) of 0.82 and an efficiency (η) of 0.91: I = 15,000 / (1.73 × 400 × 0.82 × 0.91) = about 29 A.
Treat that figure as an estimate until you find the motor data sheet, because power factor and efficiency change with motor size, speed and load.
To the motor's nameplate full load current for the actual voltage and wiring connection. In star delta starters the relay usually measures phase current and is set to FLC divided by 1.73, per the starter diagram.
The maximum time the relay allows at 7.2 times the set current: about 10, 20 or 30 seconds. It exists to ride through the starting current. Standard duties use class 10; long, heavy starts need 20 or 30.
In rough order of likelihood: real overload or mechanical drag, phase imbalance or undervoltage, wrong trip class for the start, wrong setting for the wiring connection, and only rarely a defective relay. Have a qualified electrician, wearing the PPE required for live work, measure the running current per phase before anyone touches the dial.
No. Short circuit protection comes from fuses or the circuit breaker upstream. The overload relay handles sustained overcurrent; the pair together protect the circuit and the motor.
They hold tighter tolerances, add features like phase loss detection, adjustable trip classes and trip logging outputs, and drift less over time. Bimetal relays remain perfectly serviceable for standard duties when set correctly.